China Supplier 60 kva price on line three phase low frequency ups with 5 hour backup

$1,600.00 - $5,000.00
Min. Order
3 Units
GET LATEST PRICE ON APP
Choose your specifications
Company Information

Foshan Xinchen Electronic Co., Ltd.

CN Manufacturer
Response Time
48h-72h
Response Rate:
85.7%
Transactions
---
1 Year Paid Supplier Supplier Trade Assurance
Learn More

Quick Details

Port: Foshan/Guangzhou/shenzhen
Payment Terms: L/C,T/T
Supply Ability: 100 Unit/Units per Month
Place of Origin: Guangdong China
Brand Name: MAXI
Model Number: MXD33 60KVA
Phase: Three Phase
Protection: Overload protection
Weight: 506.5KG
Type: Standby
Application: Various fields
UPS Capacity: 60kva
Product name: 3 phase online low frequency up
Wave Form: Pure Sine Wave Online Ups
Frequency: 50/60 Hz
Input Voltage Range: 380VAC
Backup time: 5hours
Power factor: 0.75
Transfer Time: 0ms
Warranty: 1 Year
Battery Voltage: 384V
Product Description

Main Features

  • High level battery reliability:
  • - Automatic battery test
  • - Battery care, Battery life span can be increased approximately by 20% more
  • Back feed protection: to avoid energy feeding back into the mains supply
  • Bypass may be deactivated to allow operation as a frequency converter (at 50 or 60 Hz), or as stabiliser
  • Easy to maintain (front access)
  • Reliable, filtered, stabilised and regulated sine wave output (double on-line concersion technology VFI according to EN50091-3 specifications) with filters for atmospheric disturbance suppression
  • UPS Application field:IT sector,Networking sector,Home appliances,Medical sector,Traffic sector,Education sector,Industrial sector,Telecom sector,Financial sector

  • UPS backup time: 5 hour backup

Products Detail

1.High reliability: IGBT technology, full microprocessor control with no-break static and manual bypass

2.High level diagnostics: event log with 128 messages, states, measurements and alarms-available from the built-in LCD in several languages

3.The UPS may be configured with the RS232 serial port (flash upgradable)

 

Electrical Specifications

1.jpg 

 

Model

60K

Crest ratio

3 : 1

                       Output frequency range

Line mode

46Hz~54Hz /56Hz~64Hz(The same as input frequency)

50Hz/60Hz (Line frequency>(54Hz /64Hz) or line frequency<(46Hz/56Hz)

Battery mode

(50+0.1) Hz/(60+0.1) Hz

Slew rate

1 Hz/Sec

                     Efficiency

Line mode

> 90%

Battery mode

> 93%

                     Overload function

Line mode/ Battery mode

Overload warning only; 105%±5%≤load

2Min, then transfer to bypass and alarm; 105%±5%

 

30S, then transfer to bypass and alarm; 125%±5%

 

0.5S, then transfer to bypass and alarm; load>150%±5%

Automatically recovery

Yes

                      Short protection

Line mode/ Battery mode

Cut off output after 3s

                      Transfer time

Line mode to Battery mode

0mS

Battery mode to line mode

0mS

Line mode to Bypass mode

<1mS

Bypass mode to line mode

<1mS

                       Battery and Charger

                       Battery

Rated voltage

384VDC

                      Protection

Low battery alarm/recovery

(361.6V±4V)/ (377.6V±4V)

Battery shutdown voltage

(320V±4V)/ (336V±4V)

                      Battery protection

Battery overcharge protection

(475V±4V)

                      Battery detect

Battery missing

Support

Battery failure

Support

                     Charge

Float charge voltage

(440±2)VDC

Charge time

Depending on the battery capacity

Charge current

10A ( Adjustable )

                     Interface

Alarm mute

Support

DC boot

Support

Auto Reboot

Support

                      Alarm function

Battery mode

Beep once every 4 second

Low battery voltage / Charger fault

Beep once every second