$30,000.00 - $80,000.00
Min. Order : 1 Set

400V 3000kW Resistive load bank For Generator Testing

Get Latest Price
Trade Assurance
Built-in order protection service in alibaba.com
Product quality
On-time shipment
More on shipping and other trade services.

Quick Details

Port: Xin'Gang,Tianjin
Payment Terms: L/C,D/A,D/P,T/T,Western Union
Supply Ability: 10 Set/Sets per Month
Cooling: Forced air cooling by fan
Place of Origin: Hebei China
Output Type: AC Three Phase
Duty cylce: Continuous
Enclosure: 20FT ISO Container
Model Number: AC400-3000kW
Max Load Power: 3000KW
Name: 400V 3000kW Resistive load bank For Generator Testing
Rated Voltage: AC400,400V,3phase, 50HZ/60HZ
Brand Name: triumph load
Function: test electrical parameter of power supply
Cooling Type: Forced air cooling
Control mode: local/remote/PC
Frequency: 50HZ/60HZ
Rated Power: 3000kW
Application: Generator Test
Packaging Detail: ISO container
Hebei Kaixiang Electrical Technology Co., Ltd
Supplier
CN
Manufacturer, Trading Company
78.6%
Response Rate
100.0%
On-time delivery rate
-
-
Transactions
101-200
Employees
11-20
R&D staffs
0
Patents
Visit Store

 

Product Description

 

1.Outdoor Stationary Load Banks

Outdoor Stationary Load Banks offer the most robust, high-capacity, outdoor designs in the industry. It is setting the standard with intelligent operating controls, safety indication layouts, adjustable load step resolution, and ease of installation. It is the perfect solution for regularly scheduled testing and commissioning of mission-critical standby emergency power systems.

 

2.Main features and advantages

 

  1. Power consumption components adopt special alloy resistor, high-temperature resisting, small thermal drift, safe and reliable. Running temperature is 1/3 of design temperature.
  2. Industrial heavy duty blower, horizontal inlet, vertical exhaust, low noise.
  3. Weather-proof structure, suitable for abominable environment.
  4. Multiple control mode: (1)Local panel control, (2)Remote control box/cabinet(3) Intelligent control(by PC software)
  5. Multiple protection function: overvoltage, overcurrent, overheat, low over blowing rate, blower overheat, blower phase sequence reverse protection, smoke alarm etc.
  6. Integrated design, easy to installation.

3.Technical Parameter

 

AC400-3000kW Intelligent Load Bank

Rating Voltage/Frequency

400VAC 50/60Hz, 3 phase 4 wire, line voltage 400V, phase voltage 230V

Rated Load Power

Resistive load: 3000kW

Installed Capacity

Resistive load: 3000kW

Load Step

10,20,20,50,100,200kW*14, total 19 steps, min step load: 1kW.

PF(Power Factor)

1

Load Tolerance (each step)

±5%

Load Tolerance(overall)

±3%

Display Precision

0.5 class

Control Power

380VAC 50Hz 3 phase 4 wire (Line voltage 380V, phase voltage 220VAC)

Wire Connection

Load power supply input——Copper bar (star coupling)

Control power supply input——Connector-bar

Insulation

F

Way of Working

Continuous Working

Casing Dimensions and Cooling

Forced air cooling,Horizontal inlet air,Vertical cooling

6058*2438*2591mm (L*W*H) 20’GP container type.

Weight

About 7000kgs

Transportation

Hoisting, there are lifting lug in top of casing

Casing Color

Grey(RAL7035)

Operating Environment Parameter

Workplace

Outdoor

Ambient Temperature

-10~+50

Relative Humidity

≤95%

Altitude

≤2500 meter

Atmospheric Pressure

86~106kPa

Brands of Main Components

Contactor

Schneider

Fuse

DELIXI

Alloy Resistance

Kaixiang(self-developed)

 4.Pictures