$0.10 - $3.30
Min. Order : 1000 Meters

1 Sqmm low voltage 5 core H07VV-U class solid copper core PVC insulation control cable

Get Latest Price
Trade Assurance
Built-in order protection service in alibaba.com
Product quality
On-time shipment
More on shipping and other trade services.

Quick Details

Port: Qingdao
Payment Terms: L/C,Western Union,T/T,MoneyGram
Supply Ability: 2000 Kilometer/Kilometers per Month
Jacket: PVC
Place of Origin: Henan China
Sample: Offered
Product Name: Control Cable
Standard: BS IEC SANS DIN
Model Number: H07VV-U
MOQ: 2000 Meters
Brand Name: CJDL
Insulation Material: PVC
OEM: Support
Voltage: 450/750V
Conductor Material: Copper
Conductor: Copper
Application: Industrial,Industrial
Core: 5 Core
Certificate: CCC
Packaging Detail: Wooden wheel as standard wrappings, or according to customer's requirements.
Package Preview: https://sc04.alicdn.com/kf/H74e942b697854977a53ae947e5819d60P.jpg_640x640.jpg,https://sc04.alicdn.com/kf/Ha1c4b4c8459d40758bb044a820637487E.jpg_640x640.jpg
Henan Changjiang Cable Co., Ltd.
Gold Supplier
CN
Manufacturer, Trading Company
≤4h
Response Time
100.0%
On-time delivery rate
US$ 30+
1
Transactions
Visit Store

5 Core H07VV-U Control Cable
Product Material
Products Description
Application:
For laying indoors,in cable trench, pipe fixed occasion. Flame retardant or Fire resistance or Low smoke and halogen free or other property can be available.
Stranded:
GB/T 9330
Structure:
Conductor:Copper
Insulation:PVC
Sheath:PVC
Using characteristic:
Rated voltage: 450/750V
Cable working temperature not higher than 70 ℃.
Short (the longest duration of no more than 5s) of the conductor temperature does not exceed 160 ℃.
Cabling ambient temperature should not be below 0 ℃, or need preheated.
Installation bending radius:
A) non-armored cable layer shall be not less than 6 times the cable diameter;
B) with armor or copper screened cable, not less than 12 times the cable diameter;
C) with a shield layer flexible cable, not less than 6 times the cable diameter.
Product Paramenters
Cores*Nominal Cross sectional Area
Strands conductor 
max diameter
Thickness of insulation
Thickness of sheath
Approximate cable diameter
Max DC 
resistance of conductor at 20 ℃
No*mm2
mm
mm
mm
mm
Ω/km
5*1
1/1.13
0.6
1.2
9.4
18.1
5*1.5
1/1.38
0.7
1.2
10.7
12.1
5*2.5
1/1.78
0.8
1.5
13.1
7.41
5*4
1/2.25
0.8
1.5
14.5
4.61
5*6
1/2.76
0.8
1.5
16.1
3.08
Recommend Products
Product Size
Manufacturing Technique
The following is the general production process of the cable for reference